Digicom 8D5684QB Guide de l'utilisateur Page 11

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 36
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 10
2.3
Pocket AL I/O QB QB Installation
Optoinsulated digital inputs
In case you use optoinsulated inputs, it will be necessary to use an external power voltage in
the range between +5V and +32Vcc.
Connect a pin of the optoinsulated digital input to positive sensor pin, then connect the other
pin of the optoinsulated digital input to negative sensor pin.
E.g.
OPT1 pin11 -> from +5Vdc to +32Vdc of sensor
OPT1 pin12 -> GND sensor
Relay outputs
The two Relay outputs of Pocket AL I/O QB allow the control of the devices that can be enabled
and disabled when a switch is closed (i.e. Light, Alarm, Logic port, etc.).
When connecting your devices, keep into consideration the maximum voltage and the maximum
power: 60Vcc – 1A.
Analog Inputs
Pocket AL I/O QB supports both active and passive 4-20mA sensors.
Passive Sensors
Pocket AL I/O QB manages passive sensors that have a maximum power of 12V. Connect the sensor between pins 3 and 4 or
between pins 5 and 6 of the 6 PIN terminal board.
GND
Sensor
Maximum Voltage
12V
4-20mA
+12V
pin
S pin
GND
pin
Active Sensors
Pocket AL I/O QB manages also active sensors that require a special power.
You can use 1 and 6 GND ground pins present on 20 pins terminal board. The 12Vdc pin will be active after you configure the
analog input.
+12V
pin
(+)
(-)
S pin
GND
GND
pin
Sensor
External power
for the sensor
4-20mA
from 5Vcc
to 32 Vcc
OPT1
pin
OPT1
pin
GND
N.A. o N.C.
pin
C
pin
GND
R
led
Rele
12V
Vue de la page 10